Operating distance
The operating distance before the equipment panel is arranged in a single row should be less than1.5m.
display distance
On the side where the personnel on duty often work, the distance from the equipment panel to the wall should not be less than 3m.
Maintenance distance
The maintenance distance behind the equipment panel should not be less than1m.
Centralized setting
The fire control room and fire fighting equipment shared with other weak current systems in the building should be centralized.