Layout requirements of fire alarm controller in fire control room
The layout of fire alarm controller in fire control room shall meet the following requirements.

Operating distance

The operating distance before the equipment panel is arranged in a single row should be less than1.5m.

display distance

On the side where the personnel on duty often work, the distance from the equipment panel to the wall should not be less than 3m.

Maintenance distance

The maintenance distance behind the equipment panel should not be less than1m.

Centralized setting

The fire control room and fire fighting equipment shared with other weak current systems in the building should be centralized.