2065438+On August 2, 2009, the fire department conducted a fire safety inspection on this KTV. During the inspection, it was found that some fire extinguishers in KTV had no compulsory certification certificate, some indoor hydrants were not equipped with fire hose reels, the linkage controller of the automatic fire alarm system was controlled manually, and only one person on duty in the fire control room was certified. In view of the above situation, the fire department punished the KTV and ordered it to suspend business for rectification on the spot. Li, the person in charge of the KTV, expressed his willingness to accept the punishment and promised to rectify it immediately. The next day coincided with the weekend. For the sake of economic benefits, Li continued to operate regardless of the requirements of suspension of business for rectification. On the same day, Liu, a drunken man in a luxury private room, threw the unlit cigarette butts in the private room on the ground and left the private room with his colleagues. For his safety, the staff accompanied him to leave. In this process, cigarette butts ignite combustible materials on the ground. Because the decoration materials in the private room are mostly combustible materials, the fire quickly spread to the whole room. Chen Mou, the patrol fire chief, shouted when he found the fire? Is there a fire? Then he fled the scene, and another fire manager, Zhang, immediately picked up the nearest fire extinguisher to put out the fire. Because he didn't change the fire extinguisher according to the requirements of the fire department, he failed to put out the fire, missed the best time to put out the fire, and finally the fire spread to the whole ballroom. After Zhang alerted Li, Li called 1 19, and the fire brigade rushed to the scene 8 minutes after receiving the alarm. After three hours of fighting, the fire was finally put out.
After the disaster investigation, it was found that when a fire broke out, the automatic fire alarm system in the building gave an alarm in time, but Zhao, the person on duty in the fire control room that day, did not have the corresponding certificate or received relevant training. Therefore, it is mistaken for equipment misoperation, and the alarm sounds are all silent. The controller is in manual state, which fails to start fire-fighting facilities such as broadcasting in the building in time.
The total accident * * * caused two people to be seriously injured, resulting in a direct economic loss of 700,000 yuan, without causing death.
?
According to the above materials, answer the following questions. (*** 18, 2 points for each question. Each question has two or more options that meet the meaning of the question, with at least 1 wrong items. Wrong choice, this question does not score; Choose one less item, and add 0.5 points for each item)
1. During the inspection, it was found that some fire extinguishers in this KTV did not have compulsory certification certificates, and the fire department ordered them to make corrections, but KTV did not make corrections. According to the provisions of the People's Republic of China (PRC) Fire Protection Law, the appropriate punishment for this behavior is ().
A. Fine 500 yuan
B. A fine of 5,000 yuan
C. A fine of 8,000 yuan
D. A fine of 2,000 yuan
E. detention
?
The initial cause of the accident was that the KTV opened without authorization when it was asked to suspend business for rectification. For this behavior, the following punishment or punishment for the responsible person Li is correct ().
A. Crime of fire accident
B. Crime of major liability accident
C. imprisonment for up to three years
D. Impose a fine of 200,000 yuan
E. impose a fine of 6,543,800 yuan.
?
3. The organization in the fire fighting and emergency evacuation plan formulated by key fire safety units shall include ().
A. Fire Action Team
B. Evacuation Steering Group
C. communication contact group
D. drilling record group
E. Organizing the command team
?
4. The following options belong to the entertainment club fire safety hidden danger is ().
A.KTV ceiling adopts porous foam sound-absorbing materials.
The number of layers in the layout of B.B.KTV is unreasonable.
C. The number of evacuation doors in luxury private rooms is insufficient
The electrical wiring of D.D.KTV does not meet the specification requirements.
E. The linkage controller of automatic fire alarm system is in manual control state.
?
5. Regarding the fire safety training for employees in the unit, the contents that must be trained according to relevant regulations are ().
A. knowledge and skills of self-help and escape
B. Fire hazards and fire prevention measures of the unit and the post.
C. Technical specifications for fire protection
D. Filling method of fire extinguisher
E. How to use fire fighting equipment
?
6. According to the relevant regulations, the following personnel who should receive special training on fire safety are ().
A. Chen Mou
B.zhao
C. Liu (surname)
D. Zhang (surname)
E.li
?
7. According to the description of the case and the relevant provisions of fire safety management, when a fire breaks out in the unit, the fire fighting and emergency evacuation plan should be implemented immediately. In this accident, the unit failed to do ().
A. put out the fire as soon as it is found.
B. Timely evacuation of personnel
C. Put out the fire with the fire brigade
D. Alarm in time
E. put the fire controller in? Automatic? Under the state.
?
8. The unit shall keep the fire fighting archives in a unified way, and the following materials shall be filed and incorporated into the fire fighting archives. The basic situation of fire safety management is ().
A. Fire reward and punishment records
B. Regular inspection records of fire control facilities
C. Fire safety system
D. fire safety training records
E. Full-time fire brigade, obligatory fire brigade personnel and their fire fighting equipment.
?
9. Zhao, the duty officer in the fire control room, failed to fulfill the duty of the duty officer in this accident. According to the general technical requirements of the fire control room, the personnel on duty in the fire control room shall perform the following duties.
A. you should hold a senior or above vocational qualification certificate.
B ensure that the automatic fire alarm system, fire extinguishing system and other linkage control equipment are in normal working condition.
C ensure that the start switch of the fire shutter distribution cabinet is in the automatic position.
D. After receiving the fire alarm, the personnel on duty shall call the police immediately.
E ensure that the outlet valve of the fire pump is locked in the normally closed position with a chain.
?